A vulnerability has been identified in TeleControl Server Basic (All versions < V3.1.2.2). The affected application is vulnerable to SQL injection through the internally used 'UnlockProjectUserRights' method. This vulnerability was discovered and disclosed on April 16, 2025, and affects the TeleControl Server Basic application, which allows remote monitoring and control of plants via WAN/LAN (Siemens Advisory, CISA Advisory).
The vulnerability is classified as a SQL injection (CWE-89) with a CVSS v3.1 base score of 8.8 (HIGH) and vector string CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H. A CVSS v4.0 base score of 8.7 has been calculated with vector string CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N. The vulnerability exists in the 'UnlockProjectUserRights' method and requires authentication and access to port 8000 on the affected system (Siemens Advisory).
A successful exploitation could allow an authenticated remote attacker to bypass authorization controls, read from and write to the application's database, and execute code with 'NT AUTHORITY\NetworkService' permissions (Siemens Advisory, CISA Advisory).
Siemens has released version V3.1.2.2 which addresses this vulnerability. As a workaround, organizations are advised to restrict access to port 8000 on affected systems to trusted IP addresses only. Siemens also recommends configuring the environment according to their operational guidelines for Industrial Security (Siemens Advisory).
Source: This report was generated using AI
Free Vulnerability Assessment
Evaluate your cloud security practices across 9 security domains to benchmark your risk level and identify gaps in your defenses.
Get a personalized demo
"Best User Experience I have ever seen, provides full visibility to cloud workloads."
"Wiz provides a single pane of glass to see what is going on in our cloud environments."
"We know that if Wiz identifies something as critical, it actually is."